FR LSH Cables

Insulation

Jaion Cables offer the best and most desirable characteristics of specially formulated polyvinyl chloride compounds. It represents a pretty high temperature and oxygen index. The index values are escalated and point to the optimum level of noncombustibility when it comes to our cables. With improved dielectric strength of high insulation resistance, our fire retardant LSH cables are able to withstand the sudden increase of load or sudden voltage surge in the electric circuit. These may also result due to irregularities within the electrical supply system. The smoke emission of the PVC-designed compound is less than 50% when you compare it to the regular kind of PVC that contains a lesser amount of acid fumes and corrosive fumes of fire that break out in abnormal situations. It may control the smooth rescue operation of the unique properties and human life.

Conductor

Created from the best grade electrolytic bright annealed copper providing maximum conductivity to the electricity flow, our conductors and PVC pipes and cables help in saving your power bills.

Our flame retardant low smoke PVC insulated and unsheathed single core cables having electrolytic grade annealed copper conductors are suitable for up to 750 volts grade. It conforms to IS: 694.

Nominal Area Of Conductor (SQ.MM) Number/Nom.dia* of Wire (MM) Nominal Thiskness of Insulation (MM) Approx. Overall Diameter (MM) Current Carrying Capacity 2 Cables, Single Phase@ Max DC Conductor Resistance At 20C Ohms/km
In Conduit Amps Unenclosed Amps
0.5 16/0.2 0.6 2.2 04 05 39.00
0.75 24/0.2 0.6 2.5 07 08 26.00
1.0 32/0.2 0.6 2.8 11 12 19.50
1.5 30/0.25 0.7 3.1 13 16 13.30
2.5 50/0.25 0.8 3.8 18 22 7.98
4.0 56/0.3 0.8 4.4 24 29 4.95
6.0 84/0.3 0.8 5.0 31 37 3.30
10.0 80/0.4 1.0 6.5 NA 46 1.91
16.0 126/0.4 1.0 7.4 NA 62 1.21
As Per Conductor Class 5 of IS:8130
25.0 196/0.4 1.2 9.3 NA 80 0.78
35.0 276/0.4 1.2 10.5 NA 102 0.554
50.0 396/0.4 1.4 12.5 NA 138 0.386
70.0 396/0.5 1.4 14.7 NA 214 0.272
95.0 475/0.5 1.6 16.7 NA 260 0.206
120.0 608/0.5 1.6 18.6 NA 305 0.161
150.0 750/0.5 1.8 20.9 NA 355 0.129
185.0 925/0.5 2.0 22.9 NA 415 0.106
240.0 1221/0.5 2.2 26.2 NA 425 0.0801
300.0 1527/0.5 2.4 29.2 NA 490 0.0641
400.0 2036/0.5 2.6 33.2 NA 590 0.0486
500.0 2540/0.5 2.8 37.3 NA 720 0.0384
630.0 3200/0.5 2.8 41.2 NA 900 0.0287

Sub sequential meter marking on cablefor sizes above 50 sq.mm

Additional Flame Retardant Low Smoke (FR-LSH) Properties
Test Specification Specified Values
Critical Oxygen Index IS 10810 Minimum 29%
Temperature Index IS 10810 Minimum 250c
Light Transmission(Smoke Density) IS 10810 Maximum 50%
Acid Gas Generation (Hydrochloric Acid) IS 10810 Maximum 20%
Colours

Our cables are available in blue, yellow, red, grey, green and black colours.

Marking

Our cables are printed with dimension, size, brand name along with voltage grade.